The interface board of a JK BMS (JIKONG BMS) provides a highly useful hardware automation feature: Dry Contacts. Unlike standard ports that output voltage, a dry contact acts as an isolated, passive switch controlled entirely by the BMS software logic.
Because it outputs no electrical potential of its own, it allows you to safely toggle external circuits—such as 12V/24V cooling fans, warning lights, external buzzers, or inverter remote switches.
This JK interface board is equipped with two independent dry contact channels that are not polarity-specific, with the pin layout shown below:
| Definition of a dry contact | |
|---|---|
| Pin number | Pin definition |
| 1 | COM1 |
| 2 | S1 |
| 3 | COM2 |
| 4 | S2 |
Each COM + S pair forms an independent dry contact loop. Under normal battery operating conditions, the circuit between COM and its corresponding S terminal is open; when the BMS triggers an alarm, overtemperature threshold or other set conditions, the COM-S circuit closes to conduct the external load circuit.
Below is the exact wiring logic and electrical rules required to implement this feature safely.
Crucial Safety Rule: Electrical Limits
⚠️ CRITICAL WARNING: The dry contact relay inside the JK interface board is designed for low-power signal switching only (typically rated up to 30V DC / 1A).
- NEVER connect high-voltage AC (e.g., 110V/220V grid power) directly to these terminals.
- NEVER connect heavy-current DC loads directly. Doing so will instantly melt the PCB trace or fuse the relay contacts shut permanently.
The Golden Rule: Always use the BMS dry contact to drive a secondary automotive or industrial relay if you are switching high-current hardware like heavy-duty fans.

Wiring Method 1: Connecting Low-Power DC Devices (Direct Wiring)
Use this configuration for small electronic buzzers or low-current 12V/24V cooling fans that draw less than 1 Amp.
Control Logic
Interrupt the Negative (“-“) line of the external power supply using one set of COM & S pins (COM1+S1 or COM2+S2).
Wiring Steps (Take Channel 1 COM1+S1 as an example)
- Connect the Positive (“+”) wire of your external DC power supply directly to the positive wire of the fan/buzzer.
- Connect the Negative (“-“) wire of your external DC power supply to Pin 1 COM1 on the JK interface board.
- Run a wire from Pin 2 S1 on the JK interface board to the negative wire of the fan/buzzer.
For a second independent load, repeat the same wiring logic with Pin 3 COM2 + Pin 4 S2.

Wiring Method 2: Connecting High-Power Devices (Using an Auxiliary Relay)
Use this setup if your cooling fan or device draws more than 1 Amp, or if you want to switch an independent secondary high-current circuit.
Control Logic
The BMS dry contact pair (COM+S) powers the coil of an external high-power automotive relay. The relay’s internal heavy-duty contacts then handle the high-current main load.
Wiring Steps (Take Channel 1 COM1+S1 as an example)
Step 1: Wire the relay coil (Pins 85 and 86 on a standard automotive relay)
- Run a jump wire from your external power Positive (“+”) to Relay Pin 85.
- Connect external power Negative (“-“) to JK Pin 1 COM1.
- Connect JK Pin 2 S1 to Relay Pin 86.
Step 2: Wire the high-power load across the relay switch (Pins 30 and 87)
- Connect heavy-gauge power Positive (“+”) to Relay Pin 30.
- Connect Relay Pin 87 to the high-power device’s positive wire.
- Route the device’s negative wire straight back to the power supply negative terminal.
To control a second separate high-power device, use the second dry contact channel COM2 (Pin3) + S2 (Pin4) to wire a second relay coil following the identical steps above.
| Parameter Specification | Example description | |||||||
|---|---|---|---|---|---|---|---|---|
| No. | Trigger | TriggerVal Unit | ReleaseVal Unit | Val Range | Note | TriggerVal | ReleaseVal | Action |
| 0 | 00 – OFF | – | – | – | – | – | ||
| 1 | 01 – Low SOC | % | % | 0~99 | TriggerVal<ReleaseVal | 25 | 30 | Turn on devices below 25%, turn off devices above 30% |
| 2 | 02 – Battery Over Voltage | mV | mV | 0~105000 | TriggerVal>ReleaseVal | 58500 | 56500 | Turn on the device above 58500mV (58.5V) and turn off the device below 56500mV (56.5V) |
| 3 | 03 – Battery Under Voltage | mV | mV | 0~105000 | TriggerVal<ReleaseVal | 40000 | 42000 | Turn on device below 40000mV (40V), turn off device above 42000mV (42V) |
| 4 | 04 – Battery Cell Over Voltage | mV | mV | 0~5000 | TriggerVal>ReleaseVal | 3620 | 3580 | Turn on the device above 3620mV (3.62V) and turn off the device below 3580mV (3.58V) |
| 5 | 05 – Battery Cell Under Voltage | mV | mV | 0~5000 | TriggerVal<ReleaseVal | 3000 | 3100 | Turn on device below 3000mV (3V), turn off device above 3100mV (3.1V) |
| 6 | 06 – Charge Over Current | mA | mA | 0~1000000 | TriggerVal>ReleaseVal | 110000 | 98000 | Turn on the device above 110000mA (110A) and turn off the device below 98000mA (98A) |
| 7 | 07 – Discharge Over Current | mA | mA | 0~1000000 | TriggerVal>ReleaseVal | 110000 | 98000 | Turn on the device above 110000mA (110A) and turn off the device below 98000mA (98A) |
| 8 | 08 – Battery over Temperature | ℃ | ℃ | -50~150 | TriggerVal>ReleaseVal | 60 | 55 | Turn on the device above 60℃ and turn off the device below 55℃ |
| 9 | 09 – MOSFET Over Temperature | ℃ | ℃ | -50~150 | TriggerVal>ReleaseVal | 90 | 85 | Turn on the device above 90℃ and turn off the device below 85℃ |
| 10 | 10 – SysAlarm | – | – | – | – | – | ||
| 11 | 11 – Battery Low Temperature | ℃ | ℃ | -50~150 | TriggerVal<ReleaseVal | -10 | 0 | Turn on device below -10℃, turn off device above 0℃ |